9 pin D-SUB female connector layout
9 pin D-SUB female connector
at the UPS
Pin Name Dir Description
1Battery ModeoutThis pin is shorted to PIN 5 (ground) if the mains power supply fails or is out of tolerance. (NORMALLY OPEN)
2---
3---
4---
5Ground-Ground terminal and common root of contacts at PIN 1, 8 and 9
6---
7UPS shut-downINIf a positive signal level (+5V to +12V DC) is applied, the UPS system switches off (PIN 5 is ground)
8Battery Capacity LowOUTThis pin is shorted to PIN 5 (ground) if the batteries have been discharged to such an extent that the remaining stored energy time is less than 2 minutes. (NORMALLY OPEN)
9Battery ModeOUTThe connection between this pin and PIN 5 (ground) is disconnected if the main power supply fails oe is out of tolerance. (NORMALLY CLOSED)
Is this document correct or incorrect?.
There are 0 reports in our database: 0 positive and 0 negative.
Pinouts.ru > Various peripheral devices pinouts > Pinout of UPS YUNTO P Series (250/500/750/1250) and layout of 9 pin D-SUB female connector
This page contain parts under Copyright © 2000-2011 by pinouts.ru team.
No portion of this webpage may be reproduced in any form without providing visible HTML link to Pinouts.ru . Webmaster permission required in any other cases.