UPS devices  > Fiskars pinouts
Pin # Signal Type Function
1 Basic Modem Mode;
Input: RS232 high pulse 4 to 5 seconds wide 
Remote UPS off: In presence of  AC, Output will turn off for 15 seconds after conditionaldelay. In absence of AC, output is kept off until normal AC returns 
1 Serial Data Mode;
Input: RS232 data 
RS232 serial communication input. 1200 baud, 8-bit, no parity, one stop bit, one start bit, Xon/Xoff 
2 Basic Mode;
Output: RS232 level high 
AC Input failure 
2 Serial Data Mode;
Output: RS232 data
RS232 serial communication output. Same as input
3 Output: Open collector transistor ON, 50 mA. 40 VDC rating AC Input failure
4 Signal Common Signal Common
5 Output: Open collector transistor ON. SO mA. 40 VDC rating  Impending low battery
6 Input: RS232 level low (-12V) Plug and Play software enable trigger
7 Input: Relay contact or RS232 level  Remote output OFF/ON: UPS total output can be kept off with low signal or closing relay contact 
8 Output: 8 to 25 VDC, 5 W constant power (0.63 A max. @ 8V) Auxiliary Control Power
9 Chassis  Connection to chassis
9 pin D-SUB male connector layout
9 pin D-SUB male connector
at the UPS
According to 1 reports in our database (1 positive and 0 negative) this pinout should be correct.

Is this pinout
Fiskars PowerRite UPS port visual pinout:
Fiskars PowerRite UPS port diagram
click to enlarge