Pinouts >  ИБП  >  HP pinouts
9 pin D-SUB male connector layout
Разъем 9 pin D-SUB male
Pin# Signal Type Function
1 RS-232 Earth Ground Signal Common for all RS-232 port signals (earth ground referenced)
2 RS-232 Transmit Output  Serial communication mode - output signal line. 
3 RS-232 Receive Input / Shutdown Serial communication mode - input signal line. Contact Closure mode - shuts down UPS if signal is held high (RS-232 level) for 200 milliseconds while UPS is operating in battery mode.
4 AC Line Fail (normally closed) Contact Closure mode - opened when AC line fails and UPS is operating in battery mode (breaks connection between Pin#4 and Pin#5).
5 Contact Closure Common / RS-232  Common Signal Common for all Contact Closure group / RS-232 Signal Common line.
7 Low Battery (normally open) Contact Closure mode - closed when remaining on-battery runtime drops below the under-defined time limit (makes connection between Pin#7 and Pin#5).
9 AC Line Fail (normally open)  Contact Closure mode - closed when in battery mode (makes connection between Pin#9 and Pin#5).
На эту распиновку нет ни одного отзыва! Если вы знаете, правильная она или нет, - нажмите на соответствующую кнопку ниже.

Эта распиновка
Copyright © 2000-2023 by pinouts.ru team, except user uploaded images.
No portion of this webpage may be reproduced in any form without visible link to pinouts.ru .
Efforts have been made to ensure this page is correct, but it is the responsibility of the user to verify the data is correct for their application.